BJA36070 - Square D - PowerPacT B I-Line Molded Case Circuit Breaker - 70 Amp - 3 Pole - 600 Volt

BJA36070 - Square D - PowerPacT B I-Line Molded Case Circuit Breaker - 70 Amp - 3 Pole - 600 Volt

New
$744.99
Sale price  $744.99 Regular price 
Skip to product information
BJA36070 - Square D - PowerPacT B I-Line Molded Case Circuit Breaker - 70 Amp - 3 Pole - 600 Volt

BJA36070 - Square D - PowerPacT B I-Line Molded Case Circuit Breaker - 70 Amp - 3 Pole - 600 Volt

$744.99
Sale price  $744.99 Regular price 

Product images are representative only. Actual product may vary.

ConditionNew

The Square D BJA36070 is a 70A, 3-pole PowerPacT B-Frame molded case circuit breaker with an I-Line plug-in line-side connection, rated 600Y/347VAC and built for Square D I-Line panelboards and switchboards.

This thermal-magnetic breaker delivers fixed Long-Time and Instantaneous (LI) protection with a 65kA interrupting rating at 480VAC. Dual-break rotating contacts limit peak let-through current during a short circuit, and the 80%-rated B-Frame body packs full capacity into roughly two-thirds the footprint of legacy Square D F-Frame breakers — so it drops straight into existing I-Line mounting space during retrofits and panel expansions. It is the designated replacement for the discontinued FH36070. Line side uses I-Line jaws with ABC phase sequence; load side ships with mechanical lugs and a push-to-trip test button.

Specifications

Brand Square D / Schneider Electric
Series PowerPacT B-Frame, I-Line, Type BJ
Part Number BJA36070
Amperage 70A (125A frame)
Voltage 600Y/347VAC, 480VAC, 480Y/277VAC, 240VAC, 208Y/120VAC, 250VDC
Poles 3
Phase 3
AIC Rating 100kA @ 208Y/120VAC, 100kA @ 240VAC, 65kA @ 480VAC and 480Y/277VAC, 25kA @ 600Y/347VAC, 50kA @ 250VDC (UL 489)
Mounting Style I-Line Plug-In
Terminal Type I-Line jaws on line side, mechanical lugs on load side
Phase Sequence ABC
Continuous Current Rating 80%
For Use With Square D I-Line Panelboards, Switchboards, and Busway Plug-In Units
Trip Technology Thermal Magnetic (LI — Long-Time, Instantaneous)
Trip Adjustability Fixed Thermal / Fixed Magnetic
Wire Range #14 AWG – 2/0 AWG (Al/Cu)
Replaces Square D FH36070 and legacy F-Frame I-Line breakers, per Schneider F-Frame to B-Frame conversion
Available Options Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Rotary Handle, Terminal Shields
Standards UL 489, CSA C22.2 No. 5, IEC 60947-2, IEC 60947-5-1, NEMA AB 1, NMX J-266, GB 14048.2
Approvals UL, CSA, CE, CCC, EAC, IEC, NOM, UKCA
Operating Temperature -25°C to 70°C
Shipping Dimensions 14 x 10 x 10 in
Shipping Weight 8 lb
Condition New

Frequently Asked Questions

What is the interrupting rating of the BJA36070?

65kA at 480VAC, 100kA at 240VAC, 25kA at 600Y/347VAC, and 50kA at 250VDC. The "J" in the catalog number identifies this 65kA interrupting class.

What does BJA36070 stand for?

B = PowerPacT B-Frame, J = 65kA interrupting rating at 480VAC, A = I-Line plug-in with ABC phase sequence, 3 = 3 poles, 6 = 600V class, and 070 = 70 amps.

What older Square D breaker does the BJA36070 replace?

It is the current replacement for the discontinued FH36070 and other legacy F-Frame I-Line breakers. The B-Frame keeps the same I-Line mounting space, so it retrofits into existing I-Line panelboards without modifying the bus.

Is the BJA36070 trip setting adjustable?

No. It uses a fixed thermal and fixed magnetic (LI) trip unit, so the 70A rating is not field-adjustable.

How does the BJA36070 connect on the line and load sides?

The line side uses I-Line jaws that plug directly onto the panelboard bus. The load side is supplied with mechanical lugs accepting #14 AWG through 2/0 AWG aluminum or copper conductors.

Can the BJA36070 be used on a 600V system?

Yes, on 600Y/347VAC wye systems with a 25kA interrupting rating. It is not rated for 600V corner-grounded delta service.

Is the BJA36070 UL listed?

Yes. It is UL 489 listed and also certified to CSA C22.2 No. 5, IEC 60947-2, NOM, and CCC standards, with CE and UKCA marking.

What is the continuous load rating on a 70A BJA36070?

The breaker is 80% rated, so continuous loads should not exceed 56 amps unless the breaker is applied in an assembly specifically listed for 100% continuous duty.