HLA36025 - Square D - Molded Case Circuit Breakers I-Line Style Plug-In - 25 Amp - 3 Pole - 600 V
Product images are representative only. Actual product may vary.
Built for commercial and industrial environments, the HLA36025 is a 25A, 3-pole molded case circuit breaker from the PowerPacT H-Frame family. It provides dependable long-time and instantaneous thermal-magnetic protection and mounts into Square D I-Line panelboards and switchboards.
It comes equipped with load-side lugs that accept 14–3/0 AWG conductors. With a 600VAC rating and a 100 kAIC capacity at 480V, this current-limiting breaker includes a Visi-Trip indicator.
Product Specifications
| Brand | Square D / Schneider Electric |
| Series | HLA (PowerPacT H-Frame) |
| Part Number | HLA36025 |
| Amperage | 25A |
| Voltage | 240VAC, 480VAC, 600VAC, 250VDC, 500VDC |
| Poles | 3 |
| AIC Rating | 125kA @ 240VAC, 100kA @ 480VAC, 50kA @ 600VAC, 20kA @ 250VDC, 50kA @ 500VDC |
| Mounting Style | I-Line Plug-In |
| Terminal Type | Lugs |
| For Use With | Square D I-Line Panelboards, Switchboards |
| Trip Technology | Thermal Magnetic (Non-Interchangeable) |
| Trip Function | LI – Long-Time, Instantaneous (Fixed Thermal, Fixed Magnetic) |
| Wire Range | 14 AWG – 3/0 AWG (Al/Cu) |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch |
| Accessories | Shunt Trip 120VAC |
| Standards | CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489 |
| Approvals | CE, CSA, HACR, NOM, UL |
| Temp Rating | -25°C to 70°C |
| Construction Features | Current Limiting, HACR Rated, Visual Trip Indicator, Non-Interchangeable Trip, 80% Rated, Mercury Free, PVC Free |
Why Choose the Square D HLA36025?
- High Interrupting Capacity: 100 kAIC at 480VAC handles demanding faults.
- Load-Side Lugs Included: Accepts 14–3/0 AWG conductors.
- 80% Rated, HACR Rated: Suited for continuous commercial loads.
- Mercury & PVC Free: Meets modern environmental construction standards.
Common Applications
- Commercial and industrial power distribution panels
- Lighting and small motor circuits
- Manufacturing and process control systems
- Switchboard and panelboard retrofits
Frequently Asked Questions
What panels is the HLA36025 compatible with?
Square D I-Line panelboards and switchboards that accept plug-in breakers.
What is the interrupting rating of the HLA36025?
100 kA at 480VAC, 125 kA at 240VAC, and 50 kA at 600VAC and 500VDC.
What wire sizes does it accept?
14–3/0 AWG, copper or aluminum, via included load-side lugs.
Does it include a shunt trip?
A 120VAC shunt trip accessory is available.
Is this a new unit?
Yes — this listing (SKU HLA36025-N) is new-in-box and ready for immediate installation.