PDG23M0040TFFL - Eaton - Molded Case Circuit Breakers Feed-Thru - 40 Amp - 3 Pole - 600 Volt

PDG23M0040TFFL - Eaton - Molded Case Circuit Breakers Feed-Thru - 40 Amp - 3 Pole - 600 Volt

New
$574.99
Sale price  $574.99 Regular price 
Skip to product information
PDG23M0040TFFL - Eaton - Molded Case Circuit Breakers Feed-Thru - 40 Amp - 3 Pole - 600 Volt

PDG23M0040TFFL - Eaton - Molded Case Circuit Breakers Feed-Thru - 40 Amp - 3 Pole - 600 Volt

$574.99
Sale price  $574.99 Regular price 

Product images are representative only. Actual product may vary.

ConditionNew

The Eaton PDG23M0040TFFL is a 40A, 3-pole molded case circuit breaker from the Power Defense Frame 2 series, configured with standard terminals on the load side only.

This globally-rated, thermal-magnetic breaker delivers fixed Long-Time and Instantaneous (LI) protection with a 65kA interrupting rating at 480VAC. It replaces older Eaton HFD3040 units and mounts into Power Defense panelboards, switchboards, and enclosures.

Specifications

Brand Eaton / Cutler-Hammer
Series Power Defense, Frame 2, Type PDG
Part Number PDG23M0040TFFL
Amperage 40A
Voltage 240VAC, 480VAC, 600VAC, 250VDC
Poles 3
Phase 3
AIC Rating 100kA @ 240VAC, 65kA @ 480VAC, 25kA @ 600VAC, 22kA @ 250VDC
Mounting Style Bolt-On / Panel Mount
Terminal Type Standard lugs, load side only
For Use With Eaton Power Defense Panelboards, Switchboards, Enclosures
Trip Technology Thermal Magnetic (LI — Long-Time, Instantaneous)
Trip Adjustability Fixed Thermal / Fixed Magnetic
Wire Range 14 AWG – 1/0 AWG (Al/Cu)
Replaces Eaton HFD3040
Standards UL 489, CSA C22.2 No. 5, IEC 60947-2, RoHS
Temperature Rating -20°C to 70°C
Package Dimensions 10 in x 8 in x 8 in (PDG box)

Frequently Asked Questions

What older breaker does the PDG23M0040TFFL replace?

It replaces the legacy Eaton HFD3040.

How is the PDG23M0040TFFL different from the TFFJ version?

The TFFL has load-side lugs only. The TFFJ includes standard lugs on both the line and load sides.

What is the interrupting rating of the PDG23M0040TFFL?

65kA at 480VAC, 100kA at 240VAC, and 25kA at 600VAC.

Is the PDG23M0040TFFL trip setting adjustable?

No. It uses a fixed thermal and fixed magnetic (LI) trip, so the 40A rating is not field-adjustable.