HJA36080 - Square D - PowerPacT H I-Line Molded Case Circuit Breaker - 80 Amp - 3 Pole - 600 Volt

HJA36080 - Square D - PowerPacT H I-Line Molded Case Circuit Breaker - 80 Amp - 3 Pole - 600 Volt

New
$824.99
Sale price  $824.99 Regular price 
Skip to product information
HJA36080 - Square D - PowerPacT H I-Line Molded Case Circuit Breaker - 80 Amp - 3 Pole - 600 Volt

HJA36080 - Square D - PowerPacT H I-Line Molded Case Circuit Breaker - 80 Amp - 3 Pole - 600 Volt

$824.99
Sale price  $824.99 Regular price 

Product images are representative only. Actual product may vary.

ConditionNew

The Square D HJA36080 is an 80A, 3-pole PowerPacT H-Frame molded case circuit breaker with an I-Line plug-in line-side connection, rated 600VAC and built for Square D I-Line panelboards and switchboards.

This thermal-magnetic breaker provides fixed Long-Time and Instantaneous (LI) protection with a 65kA interrupting rating at 480VAC and 100kA at 240VAC. Current-limiting construction reduces peak let-through energy during a short circuit, protecting downstream conductors and gear. The H-Frame occupies the same I-Line mounting space as Square D's discontinued F-Frame breakers, making it a straight plug-on replacement for the FC36080 and FH36080. A Visi-Trip indicator flags a fault trip on sight, and the ABC phase-sequence jaws seat directly onto the panelboard bus.

Specifications

Brand Square D / Schneider Electric
Series PowerPacT H-Frame, I-Line, Type HJ
Part Number HJA36080
Amperage 80A (150A frame)
Voltage 600VAC, 480VAC, 240VAC, 250VDC
Poles 3
Phase 3
AIC Rating 100kA @ 240VAC, 65kA @ 480VAC, 25kA @ 600VAC, 20kA @ 250VDC (UL 489)
Mounting Style I-Line Plug-In
Terminal Type I-Line jaws on line side, mechanical lugs on load side
Phase Sequence ABC
Continuous Current Rating 80%
For Use With Square D I-Line Panelboards and Switchboards
Trip Technology Thermal Magnetic (LI — Long-Time, Instantaneous)
Trip Adjustability Fixed Thermal / Fixed Magnetic
Wire Range #14 AWG – 3/0 AWG (Al/Cu)
Replaces Square D FC36080, FH36080
Available Options Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Motor Operator, Rotary Handle
Standards UL 489, CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1
Approvals UL, CSA, CE, IEC, NOM
Construction Features Current Limiting, HACR Rated, Visi-Trip Indicator
Operating Temperature -25°C to 70°C
Shipping Dimensions 14 x 10 x 10 in
Shipping Weight 8 lb
Condition New

Frequently Asked Questions

What is the interrupting rating of the HJA36080?

65kA at 480VAC, 100kA at 240VAC, 25kA at 600VAC, and 20kA at 250VDC.

What does HJA36080 stand for?

H = PowerPacT H-Frame, J = 65kA interrupting rating at 480VAC, A = I-Line plug-in with ABC phase sequence, 3 = 3 poles, 6 = 600V class, and 080 = 80 amps.

Which older Square D breakers does the HJA36080 replace?

It replaces the discontinued FC36080 and FH36080. The H-Frame keeps the same I-Line mounting dimensions, so it plugs into existing panelboards without bus work.

Is the HJA36080 trip setting adjustable?

No. The 80A HJA uses a fixed thermal and fixed magnetic (LI) trip unit.

Is the HJA36080 current limiting?

Yes. It limits peak let-through current and I²t energy during a short circuit, which reduces stress on downstream conductors and supports tighter series-rated combinations.

What wire sizes do the load lugs accept?

The supplied mechanical lugs accept #14 AWG through 3/0 AWG aluminum or copper conductors.

What is the continuous load limit for the HJA36080?

At 80% rating, continuous loads should not exceed 64 amps unless the breaker is installed in an assembly listed for 100% continuous duty.

Is the HJA36080 UL listed?

Yes. It is UL 489 listed and also certified to CSA C22.2 No. 5, IEC 60947-2, and NOM, with CE marking.