Square D JDA36200 200 Amp 3-Pole 600V Molded Case Circuit Breaker I-Line Plug-In

JDA36200 - Square D - Molded Case Circuit Breaker I-Line Plug-In - 200 Amp - 3 Pole - 600 Volt

New
$914.99
Sale price  $914.99 Regular price 
Skip to product information
Square D JDA36200 200 Amp 3-Pole 600V Molded Case Circuit Breaker I-Line Plug-In

JDA36200 - Square D - Molded Case Circuit Breaker I-Line Plug-In - 200 Amp - 3 Pole - 600 Volt

$914.99
Sale price  $914.99 Regular price 

Product images are representative only. Actual product may vary.

The Square D JDA36200 is a 200 Amp, 3-pole, 600 Volt molded case circuit breaker built for I-Line plug-in mounting in Square D panelboards and switchboards. It uses thermal-magnetic trip technology for reliable overcurrent protection and serves as the direct replacement for the discontinued KA36200, making it a drop-in upgrade for existing I-Line distribution equipment.

Key Features

  • 200A rated, 3-pole, 3-phase molded case circuit breaker
  • Voltage rated 240VAC, 480VAC, 600VAC, and 250VDC
  • Thermal-magnetic trip with adjustable magnetic trip setting for fine-tuned protection
  • 25kA AIC at 240VAC (18kA @ 480VAC, 14kA @ 600VAC, 20kA @ 250VDC)
  • Visi-Trip indicator for fast visual fault identification
  • I-Line mounting style, compatible with Square D I-Line panelboards and switchboards
  • UL 489 listed, HACR rated, current limiting, mercury-free and RoHS compliant
  • Direct replacement for the discontinued Square D KA36200

Specifications

Brand Square D / Schneider Electric
Series JDA
Part Number JDA36200
Amperage 200A
Voltage 240VAC, 480VAC, 600VAC, 250VDC
Poles 3
Phase 3
AIC Rating 25kA @ 240VAC, 18kA @ 480VAC, 14kA @ 600VAC, 20kA @ 250VDC
Mounting Style I-Line
Terminal Type Lugs
For Use With Square D I-Line Panelboards, Switchboards
Trip Technology Thermal Magnetic
Trip Function Code LI (Long-Time, Instantaneous)
Trip Adjustability Fixed Thermal, Adjustable Magnetic
Wire Gauge 3/0 AWG - 350 kcmil (Al/Cu)
Available Options Shunt Trip, Auxiliary Switch, Alarm Switch, Undervoltage Release, Padlock Attachment
Accessories Load Side Lugs Included
Standards CSA C22.2 No. 5, HACR, IEC 60947-2, NEMA AB 1, UL 489
Approvals CCC, CE, CSA, IEC, NOM, UKCA, UL
Temp Rating -25C to 70C
Construction Features HACR Rated, Current Limiting, Visual Trip Indicator, Non-Interchangeable Trip, Reverse Feed, Mercury Free, RoHS Compliant, PVC Free

Frequently Asked Questions

What is the Square D JDA36200 used for?
It protects 200A, 3-pole electrical circuits from overcurrent and short-circuit faults in commercial and industrial systems using Square D I-Line panelboards or switchboards.

Is the JDA36200 a replacement for the KA36200?
Yes. The JDA36200 is Square D's designated direct replacement for the discontinued KA36200, so it installs into existing I-Line equipment without modification.

What is the AIC rating of the JDA36200?
25kA at 240VAC, 18kA at 480VAC, 14kA at 600VAC, and 20kA at 250VDC.

Does the JDA36200 have an adjustable trip?
Yes, it has a fixed thermal trip and an adjustable magnetic trip setting.

You may also like