PDG23G0150TFFL - Eaton - Molded Case Circuit Breakers Feed-Thru - 150 Amp - 3 Pole - 600 Volt
Product images are representative only. Actual product may vary.
The Eaton PDG23G0150TFFL is a 150A, 3-pole molded case circuit breaker from the Power Defense Frame 2 series, configured with standard terminals on the load side only.
This globally-rated, thermal-magnetic breaker delivers fixed Long-Time and Instantaneous (LI) protection at a 35kA interrupting rating at 480VAC. It is a modern upgrade path for older Eaton FD3150-series breakers and mounts into Power Defense panelboards, switchboards, and enclosures — choose this load-only configuration when the line side connects directly to a bus rather than a separate lug.
Specifications
| Brand | Eaton / Cutler-Hammer |
|---|---|
| Series | Power Defense, Frame 2, Type PDG |
| Part Number | PDG23G0150TFFL |
| Amperage | 150A |
| Voltage | 240VAC, 480VAC, 600VAC, 250VDC |
| Poles | 3 |
| Phase | 3 |
| AIC Rating | 65kA @ 240VAC, 35kA @ 480VAC, 18kA @ 600VAC, 10kA @ 250VDC |
| Mounting Style | Bolt-On / Panel Mount |
| Terminal Type | Standard lugs, load side only |
| For Use With | Eaton Power Defense Panelboards, Switchboards, Enclosures |
| Trip Technology | Thermal Magnetic (LI — Long-Time, Instantaneous) |
| Trip Adjustability | Fixed Thermal / Fixed Magnetic |
| Wire Range | 4 AWG – 4/0 AWG (Al/Cu) |
| Replaces | Eaton FD3150-series (upgrade path) |
| Standards | UL 489, CSA C22.2 No. 5, IEC 60947-2, RoHS |
| Temperature Rating | -20°C to 70°C |
| Package Dimensions | 10 in x 8 in x 8 in (PDG box) |
Frequently Asked Questions
How is the PDG23G0150TFFL different from the TFFJ version?
The TFFL has lugs on the load side only. The TFFJ includes standard lugs on both the line and load sides.
What is the AIC rating of the PDG23G0150TFFL?
35kA at 480VAC, 65kA at 240VAC, and 18kA at 600VAC.
What does the PDG23G0150TFFL replace?
It is the modern upgrade path for older Eaton FD3150-series breakers.
When should I choose the load-side-only configuration?
Choose TFFL when the line side of the breaker lands directly on a panelboard or switchboard bus and does not require a separate line lug.