Description
Built for commercial power distribution, the Square D HJA36035 is a 3-pole, 35A MCCB. It utilizes fixed thermal and magnetic trip elements to deliver dependable LI protection. Featuring an I-Line connection, it mounts into compatible Square D panelboards and switchboards. It is an ideal substitute for older FC36035, FH36035, and FA36035 catalog numbers. With a 65 kAIC rating at 480VAC, this current-limiting device includes a Visi-Trip indicator for quick fault identification.Specifications
| Brand | Square D |
| Series | HJA |
| Part Number | HJA36035 |
| Amperage | 35A |
| Voltage | 240VAC, 480VAC, 600VAC, 250VDC |
| Poles | 3 |
| Phase | 3 |
| AIC Rating | 100kA @ 240VAC, 65kA @ 480VAC, 25kA @ 600VAC, 20kA @ 250VDC |
| Mounting Style | I-Line |
| Terminal Type | Lugs |
| For Use With | Square D I-Line Panelboards, Square D I-Line Switchboards |
| Trip Technology | Thermal Magnetic |
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Wire Gauge | 14 AWG-3/0 AWG |
| Max Wire | 3/0 AWG |
| Min Wire | 14 AWG |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Motor Operator |
| Accessories | Load Side Lugs Included |
| Standards | CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489 |
| Approval | CE, CSA, HACR, IEC, NOM, UL |
| Temp Rating | -25C to 70C |
| Construction Features | HACR Rated, Current Limiting, Visual Trip Indicator, Reverse Feed, Non-Interchangeable Trip |